A 25-Metre Extension Lead Loses Four Per Cent of the Voltage
Gepubliceerd op 12-11-2026 · 3 min leestijd · Dagelijkse calculators
Marco Bianchi — Redacteur wonen, klussen en auto bij OneKitly
Verbouwen · Materialen
Getoetst aan 2 bronnen
Cable resistance is resistivity times length divided by cross-section, and the length that counts is the round trip. A 25-metre extension lead in 1.5 mm² copper therefore contains 50 metres of conductor and measures 0.583 ohms. Pull 16 amps through it — a big circular saw, a heat gun, a small welder — and 9.3 volts are dropped along the way, leaving 221 at the socket instead of 230. Those volts do not vanish: they appear as 149 watts of heat spread through the drum, which is exactly why the instructions say to unwind the cable fully before drawing a heavy load.
Fifty metres of 1.5 mm² copper is 0.583 Ω. Draw 16 A through it and 9.3 volts never reach the tool — they heat the cable instead, at 149 watts.
Why the drum is the dangerous part
The 149 watts exist whether the cable is coiled or laid out; what changes is where the heat can go. Spread along 25 metres of floor it is six watts per metre and disappears into the air. Wound into a drum it is 149 watts inside a plastic cylinder with almost no surface exposed, and the middle turns can pass 60 °C within minutes. Coiled leads on drums carry two current ratings for this reason — one wound, one unwound — and the wound figure is often less than half the other.
What the missing volts do to the tool
A universal motor loses power roughly with the square of the voltage, so 4% less voltage is about 8% less power at the blade — noticeable but survivable. What suffers more is anything with a starting surge: a compressor or a large saw pulls several times its running current for a moment, and the same cable drops several times as many volts during that instant, sometimes enough to stall the start entirely. The classic symptom is a tool that runs fine on a short lead and refuses to start on a long one, with no fault anywhere in either.
| Cable | Resistance | Volts lost |
|---|---|---|
| 25 m of 1.5 mm² | 0.583 Ω | 9.3 V |
| 25 m of 2.5 mm² | 0.350 Ω | 5.6 V |
| 5 m of 2.5 mm² | 0.070 Ω | 1.1 V |
Uitgewerkt met onze eigen calculator
Calculator draadweerstand
Gegeven
- Lengte (m)
- 10
- Doorsnede (mm²)
- 2,5
- Materiaal
- Koper
Resultaat
- Weerstand (Ω)
- 0,07
Deze cijfers komen uit de calculator hieronder, ze zijn niet met de hand ingetypt — ze worden opnieuw berekend telkens als de tool verandert.
Reken het door met je eigen cijfers →Veelgestelde vragen
- Does aluminium wiring change the numbers much?
- Aluminium has 60% more resistivity than copper, so the same size cable loses 60% more voltage and a cable has to be one size larger to match. It is used anyway in long distribution runs because it is far lighter and cheaper per metre, and the extra cross-section costs less than the copper it replaces. In a house, aluminium branch wiring has a poor history around terminations rather than in the middle of a run, since it creeps and oxidises at screw connections in a way copper does not.
- How long can a lead be before it matters?
- The usual design target is to keep the drop under 3% for lighting and 5% for power, which on a 16 A circuit in 2.5 mm² allows about 51 metres of cable — 103 metres of conductor there and back. Below 5 amps almost nothing matters at household distances: a laptop charger on a hundred metres of thin lead is fine, because the current is what turns resistance into a problem, not the length by itself. The question to ask is never how long the lead is but how many amps are going down it.
Artikelen die je misschien interesseren
Alle gidsen →Vergelijkbare tools
Bronnen
Een fout in dit artikel gezien?