Kort gezegd

Cable resistance is resistivity times length divided by cross-section, and the length that counts is the round trip. A 25-metre extension lead in 1.5 mm² copper therefore contains 50 metres of conductor and measures 0.583 ohms. Pull 16 amps through it — a big circular saw, a heat gun, a small welder — and 9.3 volts are dropped along the way, leaving 221 at the socket instead of 230. Those volts do not vanish: they appear as 149 watts of heat spread through the drum, which is exactly why the instructions say to unwind the cable fully before drawing a heavy load.

Advertentie

Fifty metres of 1.5 mm² copper is 0.583 Ω. Draw 16 A through it and 9.3 volts never reach the tool — they heat the cable instead, at 149 watts.

Why the drum is the dangerous part

The 149 watts exist whether the cable is coiled or laid out; what changes is where the heat can go. Spread along 25 metres of floor it is six watts per metre and disappears into the air. Wound into a drum it is 149 watts inside a plastic cylinder with almost no surface exposed, and the middle turns can pass 60 °C within minutes. Coiled leads on drums carry two current ratings for this reason — one wound, one unwound — and the wound figure is often less than half the other.

What the missing volts do to the tool

A universal motor loses power roughly with the square of the voltage, so 4% less voltage is about 8% less power at the blade — noticeable but survivable. What suffers more is anything with a starting surge: a compressor or a large saw pulls several times its running current for a moment, and the same cable drops several times as many volts during that instant, sometimes enough to stall the start entirely. The classic symptom is a tool that runs fine on a short lead and refuses to start on a long one, with no fault anywhere in either.

Resistance
Extension leads at 16 amps
CableResistanceVolts lost
25 m of 1.5 mm²0.583 Ω9.3 V
25 m of 2.5 mm²0.350 Ω5.6 V
5 m of 2.5 mm²0.070 Ω1.1 V

Uitgewerkt met onze eigen calculator

Calculator draadweerstand

Gegeven

Lengte (m)
10
Doorsnede (mm²)
2,5
Materiaal
Koper

Resultaat

Weerstand (Ω)
0,07

Deze cijfers komen uit de calculator hieronder, ze zijn niet met de hand ingetypt — ze worden opnieuw berekend telkens als de tool verandert.

Reken het door met je eigen cijfers →
Advertentie

Veelgestelde vragen

Does aluminium wiring change the numbers much?
Aluminium has 60% more resistivity than copper, so the same size cable loses 60% more voltage and a cable has to be one size larger to match. It is used anyway in long distribution runs because it is far lighter and cheaper per metre, and the extra cross-section costs less than the copper it replaces. In a house, aluminium branch wiring has a poor history around terminations rather than in the middle of a run, since it creeps and oxidises at screw connections in a way copper does not.
How long can a lead be before it matters?
The usual design target is to keep the drop under 3% for lighting and 5% for power, which on a 16 A circuit in 2.5 mm² allows about 51 metres of cable — 103 metres of conductor there and back. Below 5 amps almost nothing matters at household distances: a laptop charger on a hundred metres of thin lead is fine, because the current is what turns resistance into a problem, not the length by itself. The question to ask is never how long the lead is but how many amps are going down it.